ABB capacitor duty contactor

By March 4, 2020 10:59 am IST

ABB capacitor duty contactor
.

UA30..RA 3-pole contactors for capacitor switching can be used in installations in which the peak current far exceeds 100 times nominal rms current. The contactors are delivered complete with their damping resistors and must be used without additional inductances. The capacitors must be discharged (maximum residual voltage at terminals ≤ 50 V) before being re-energised when the contactors are making. Their electrical durability is 2,50,000 operating cycles for Ue< 500 V and 1,00,000 operating cycles for 500 V ≤ Ue ≤ 690 V. The UA..RA contactors are fitted with a special front mounted block, which ensures the serial insertion of 3 damping resistors into the circuit to limit the current peak on energisation of the capacitor bank. Their connection also ensures capacitor pre-charging in order to limit the second current peak occurring upon making of the main poles. The insertion of resistors allows to dampen the highest current peak of the capacitor when switching on, whatever its level. The UA..RA series 3-pole contactors are of the block type design.

Main poles and auxiliary contacts: Three main poles, one built-in auxiliary contact
Control circuit: AC operated with laminated magnet circuit
Accessories: A wide range of accessories is available.

Capacitor transient conditions
In low-voltage industrial installations, capacitors are mainly used for reactive energy correction (raising the power factor). When these capacitors are energised, over-currents of high amplitude and high frequencies (3-15 kHz) occur during the transient period (1-2 ms). The amplitude of these current peaks, also known as “in rush current peaks”, depends on the following factors:

    Advertising

    EPR Android App Banner

    The network inductances
  • The transformer power and short-circuit voltage
  • The type of power factor correction

Application
The UA..RA contactors can be used in installations in which the peak current far exceeds 100 times nominal rms current. The contactors are delivered complete with their damping resistors and must be used without additional inductances.

For more information, visit:
R.SANGHAVI MERCANTILE PVT. LTD.
Website: www.abbdealer.com

Cookie Consent

We use cookies to personalize your experience. By continuing to visit this website you agree to our Terms & Conditions, Privacy Policy and Cookie Policy.

Nirmal Wires
Nirmal Wires
Android App
Android App

Events

Wiretech 2025
Wiretech 2025
Power Gen
Power Gen
GOTS 2025
GOTS 2025
India Green Energy Expo
India Green Energy Expo

Our Sponsors

Greenfinity Powertech Pvt Ltd
Greenfinity Powertech Pvt Ltd
Rayzon Solar Pvt Ltd
Rayzon Solar Pvt Ltd
Kp Group
Kp Group
Adani Solar
Adani Solar
Fluke
Fluke
Meco Instruments Pvt Ltd
Meco Instruments Pvt Ltd
Icon Solar-En Power
Icon Solar-En Power
Mtekpro Technologies
Mtekpro Technologies
Novasys
Novasys
Testo India
Testo India
Timken
Timken
OEN
OEN
Sun Bond
Sun Bond
Orange Power
Orange Power
S K Industrial
S K Industrial
Elev8 Lift
Elev8 Lift
flir system
flir system
Omicron
Omicron
DEIF
DEIF
Electrotherment
Electrotherment
Aeron Composite Pvt Ltd
Aeron Composite Pvt Ltd
PRAMA HIKVISION INDIA
PRAMA HIKVISION INDIA
Sun Cables
Sun Cables