Promonique
Promonique
Home » Tech View » Parameters to maintain substation earthing with calculations

Parameters to maintain substation earthing with calculations

December 20, 2021 2:50 pm

Parameters to maintain substation earthing with calculations
.

This article walks us through the key critical parameters to be considered for selecting and working on earthing systems for a substation. 

The fundamental role of any substation earthing is to dissipate the short circuit current into the earth without drying out the area and to limit the potential gradient throughout the substation to maintain the step and touch voltages within safe values. There are two features considered during the design of earthing for a substation which is:

  • Providing a low impedance path for the fault currents occurred during normal conditions and fault conditions
  • Avoiding fatal electric shocks to the person working in the vicinity of the grounded facilities

Earthing standards:

To calculate the substation earthing design parameters and the potential shock safety limits, a large variety of national and international guidelines are followed across the globe that is:

  • BS7354-1990 Code of practice for design of high-voltage open terminal stations
  • EATS 41-24-guidelines for the design, installation, testing, and maintenance of main earthing stations in substations
  • IEEE Standard 80-2000-Guidelines for AC substation grounding

Parameters considered for earthing of substation

Ground potential rise: An earthing mat is a grounding system formed by a grid of conductors buried horizontally and provide a low impedance path for the earth’s fault current to dissipate into the earth. The earthing grid present in the substation is an electrical connection to the earth at zero-potential reference point. The connection where the earth mat is buried is not ideal due to the resistivity of soil that leads to the flow of current via the grid to the earth, during a typical earth fault condition leading to a potential rise in the system, creates a potential gradient within and around the substation ground area. Ground Potential Rise (GPR) can be defined as the product of ground electrode impedance with respect to zero-earth and the current flowing through that electrode impedance.

GPR = I0 × Rg: GPR can be controlled by keeping resistance of the earthing grid as low as possible, so that the earth fault conditions are limited for maintaining the step and touch the potential limits. Step potential, mesh potential, and transferred potential plays a vital role in the calculation of an earthing system and to ensure equipment safety as well as human safety.

Step potential: The potential difference between two points on the surface of the earth separated by a distance of one pace that is normally assumed to be one meter in the direction of the maximum potential gradient is known as ‘Step Potential’. Considering a constant body impedance of 1000Ω Step potential can be calculated as

01

Where ρs – resistivity of the surface layer & ∁s – scaling factor due to the protective surface layer.

Touch potential: The potential difference between a grounded metallic structure and a point on the earth’s surface at a distance equal to the normal maximum horizontal reach is approximately one meter.

02

 

Where ρs – resistivity of the surface layer & ∁s – scaling factor due to the protective surface layer.

Transferred voltage is a special case of touch potential where the voltage generated is transferred to/from an external point to the substation.

Mesh potential: Mesh potential is the maximum touch voltage generated within a mesh of an earth grid. The mesh potential is defined as the product of the soil resistivity (ρ), the configuration of the grid (Km), a correction factor (Ki), errors that occurred due to assumptions, and the average current per unit flowing through the grounding conductor IG/L

04

Earthing system design considerations

In any Substation earthing layout, the earthing system is made up of an earthing grid consisting of cross bonded conductors. These conductors must possess the adequate thermal capacity to provide sufficient time for the fault currents to flow through them. The earthing conductors should also be mechanically sturdy and corrosive resistant. The conductors are normally buried horizontally at a depth between 0.5m to 1m ensuring the earthing conductor has adequate mechanical protection. The surroundings shall not dry out; hence, it is placed below the frost line.

Axis-12-2021 (1)

For proper designing of the earthing system, certain parameters such as the conductor size, grid resistance, and the maximum grid currents are considered.

Size of the conductor: The minimum size of a conductor required during earthing can be determined by

06

 

Where short circuit current (lfs), duration of fault current (tc), thermal resistivity (ar), soil resistivity (prl), the thermal capacity of copper (TCAP), maximum allowed temperature (Tm), and ambient temperature (Ta) are the factors affecting the size of the conductors.

Grid resistance

The fall of the potential test method is used to measure the ground grid resistance. The resistance obtained from the ratio of the earth’s potential rise and the current causing it is called the grid resistance. The grid resistance can be calculated as

13

Where A= area of the grid, p= resistivity, L = length of the grid

Maximum grid current

The maximum grid current is the ratio of current flowing between the earth grid and the surrounding earth to the symmetrical fault current. This current is affected by the fault current division factor. The maximum grid current can be calculated as:

14

Where  – current flowing through the grid,  – decrement factor

Vertically driven rods

The electrodes used when the soil resistivity of the ground is low and it can penetrate beneath the layer where the soil resistivity is high are vertically driven rods. The length of the earth rod is calculated in such a way that it reaches more stable layers into the earth below. These earth rods would stabilize the earth grid resistance during the changes in seasonal resistivity.

Substation fences

Earthing around the substation is important to avoid dangerous touch potentials and fatal electric shocks. Metallic fences are built up around the substation. These fences also prevent access to the general public. Earthing fences can be built in two ways i.e., by connecting the earth grid electrically with the fence within the grid or by independently earthing the fence and placing it outside the earth grid with an acceptably low potential gradient.

Other substation earthing

The ground potential rise at any substation can be subsided by overhead line earth wires where the wires are connected to the earth grid diverting the fault current towards the foot of the earthing tower. Cable armouring is done to divert the earth fault current towards a remote earthing grid.

Conclusion

The design of grounding in a substation is a continuous and a vital process as the safety of the equipment as well as the workers is dependent on the design parameters. Proper grounding of a substation provides a safe environment to the personnel in the vicinity of grounded facilities. There are few other elements involved in the process of designing which include the design refinement, effects of directly buried pipes, and control of power cable grounding, surge arrester grounding, and installation considerations. An ideal grounded substation is an optimally designed safe grid, designed using accurate modelling techniques, enabling material and labour savings while meeting all the safety standards. This improves field safety, better quality installation, constructability, and efficiency in all types of weather conditions.

This article is part of our series of articles on Lightning Arresters, Surge Protection and Earthing; you can read more with the following links:

Introduction to the basics of Lightning Protection and Earthing and the Standards (IEC 62305 and UL 467)

Lightning Protection System Design and Products

Surge Protection Devices (SPD) 

Lightning Protection Zones and their Application to SPD Selection

For more details, contact:
Email: info@axis-india.com
Website: www.axis-india.com
Axis, Plot No.104 C, Kandivali Co-op Industrial Estate Ltd., Kandivali (W), Mumbai-400067, Maharastra, India.

Cookie Consent

We use cookies to personalize your experience. By continuing to visit this website you agree to our Terms & Conditions, Privacy Policy and Cookie Policy.

Android App
Android App
EPR eMagazine April 2024
EPR eMagazine April 2024
EPR eMagazine April 2024

Events

RenewX India
RenewX India
International Geotechnical Innovation Conference
International Geotechnical Innovation Conference
EL Asia
EL Asia
Global Energy Digitalisation Conclave
Global Energy Digitalisation Conclave
World battery and energy storage industry expo
World battery and energy storage industry expo
Green Hydrogen Summit
Green Hydrogen Summit
POWERGEN India
POWERGEN India
Windergy
Windergy

Our Sponsors

Rayzon Solar Pvt Ltd
Rayzon Solar Pvt Ltd
Doble Engineering
Doble Engineering
Allied Power Solutions
Allied Power Solutions
Nirmal
Nirmal
KEI Industries Limited
KEI Industries Limited
Maco Corporation India Pvt Ltd
Maco Corporation India Pvt Ltd
Meco Instruments Pvt Ltd
Meco Instruments Pvt Ltd
Icon Solar-En Power
Icon Solar-En Power
Novasys
Novasys
Testo India
Testo India
Mecc-Alte India
Mecc-Alte India
Newtech Switchgear
Newtech Switchgear
Triveni Turbine ltd
Triveni Turbine ltd
Aeron Composite Pvt Ltd
Aeron Composite Pvt Ltd
Winsun
Winsun
A-1 ELECTRICALS
A-1 ELECTRICALS
Allied Moulded Enclosure Products
Allied Moulded Enclosure Products
ANUSHREE ELECTRICAL ENGINEERS
ANUSHREE ELECTRICAL ENGINEERS
Ashone Technologies
Ashone Technologies
Citroen Switchgears Pvt. Ltd.
Citroen Switchgears Pvt. Ltd.
Electrotherm
Electrotherm
KVTEK Power Systems
KVTEK Power Systems
MENNEKES Electric India
MENNEKES Electric India
Om Technical Solutions
Om Technical Solutions
PRAMA HIKVISION INDIA
PRAMA HIKVISION INDIA
Motwane Manufacturing
Motwane Manufacturing